Purpose – The purpose of this study is to investigate the incorporation of lightweight aggregate concrete modify with fiber (LWACF) in water retaining structure. In developed countries LWACF is being successfully used as structural concrete; however, third-world countries such as Pakistan are still struggling to come up with the practical applications of lightweight concrete in the building and construction industry. One reason is because of the lack of reliable data regarding its performance as a structural member in the building and construction industry. Design/methodology/approach – The present study inspected the flexural and shear tolerance of fiber-reinforced LWACF by testing six beam specimens’ cast, cured and tested after 28 days for the purpose. An overhead tank of 1,000-gallon capacity was also constructed to verify the application of LWACF by observing its water retention behavior. The experimental design included a mix design of concrete at a target strength of 21 MPa for control sample natural aggregate and for synthetic aggregate modified with polypropylene fibers. Compressive strengths of both categories of concrete were also determined by crushing the cylindrical samples at the age of 7, 14, 21 and 28 days. The cast beams were later subjected to the application of two-point loading test until failure.

Featured Image

Read the Original

This page is a summary of: Flexural and shear strengths of fiber modify lightweight aggregate concrete and its application in water-retaining structures, World Journal of Engineering, April 2017, Emerald,
DOI: 10.1108/wje-12-2016-0174.